System
CPU Freescale MPC8308 PowerPC CPU,400MHz
Memory DDR2 128M
Flash 8M NorFlash128M NandFlash
Operating System Linux 2.6.29.6
LED
NISE-P1008-F System:Power x1,RUN x1,PWR1 Alarm x1,PWR2 Alarm x1
LAN:Link x4 & Act x4 Indicators
Serial Port:Transfer x8 & receive x8 Indicators
Function LED:2 x4 Indicators
NISE-P1008-S System:Power x1,RUN x1,PWR1 Alarm x1,PWR2 Alarm x1
LAN:Link x6 & Act x6 Indicators
Serial Port Transfer x8 & receive x8 Indicators
Function LED 2 x4 Indicators
Others RTC,Buzzer,Watchdog Timer,Reset button,Console Port x1
Serial Communication
Console Port Console Port DB9 connector x1
RS232 115200Bps N,8,1
Serial Port 8 x RS232/485 TB Interface connector
Software Mode select,RS232 Signals:TXD,RXD,GND
RS485 Signals:485A(Data+),485B(Data) Baud:300~115200Bps
Protection Builtin 15KV ESD protection for all signals, 1.5KV Magnetic isolation protection
Network Communication
LAN
NISE-P1008-F Auto-sensing 10/100/1000Mbps x 2, RJ45
Auto-sensing 10/100Mbps x 2, RJ45
Build-in 1.5KV magnetic isolation protection
NISE-P1008-S Auto-sensing 10/100/1000Mbps x 2, RJ45
Auto-sensing 10/100Mbps x 4, RJ45
Build-in 1.5KV magnetic isolation protection
Optional
Digital Input Port 4 x Isolation Input
VL:≦80V VH:>85V
Digital Output Port 4 x Relay Output
VL:≦80V VH:>85V
CAN Port CAN2.0B(Isolation protection) Baud:5Kbps~1Mbps
IRIG-B Port RS-485(Isolation protection) Precision:±1us
Power Requirements
Power Input Dual Power Input Design
PWR1: 85~265VDC or 100~265VAC
PWR2: 85~265VDC or 100~265VAC
Lost power alarm Relay empty node(Limited to single power)
Power Consumption
Mechanical
Power alarm indicators
10W@220VAC
Dimensions 483(L)x226.7(W)x44(H)(Maximum size)
Installation Rack Mount 1U
Environmental
Operating Temperature -20-60℃ Storage Temperatur -30-80℃ Regulatory Approvals and Warranty
EMC GB/T 17626.2-2006 Class 4
GB/T 17626.4-2008 Class 4
GB/T 17626.5-2008 Class 4
GB/T 17626.6-2008 Class 3
Warranty 3 Years